Mechanical Engineers

 
Home | Bearing design, manufacture an | Pump engineering | Piping & fluid mechanics engin | Optical systems engineering | Mechanical Seal engineering | Mechanical engineering other t | Mechanical Acoustics/Vibration | Laser engineering
  Position:HOME>HVAC/R engineering>Article Content
Dry Cleaner Boiler Room Wall Fire rating
Source:Internet Author:Unknow Pubdate:2008-04-15  
Golestan (Mechanical) 1 Nov 07 13:55
Hi,

What is the required wall fire rating for the boiler room of a dry cleaner shop?  How about the wall rating for the entire store.  I am working on the MEP for construction of a dry cleaner as a finishout inside of an existing shell building.  Shell building is brand new.  Has fire sprinkler also.

Thanks,

stanlsimon (Mechanical) 10 Nov 07 21:50
What area are you in?, different codes give different requirements. With the sprinklers, depending on the btu input of boiler,(probably fairly small) you may not need more than two layers of sheet rock up to the deck.

Any penetrations of that wall would need to have a UL assembly listing equal to the code requirement.
 
Whoever is doing the code review needs to determine the occupancy separation which is also a function of what kind of space is next to you.  There is generally both a smoke and fire requirement.

字串3



stookeyfpe (Specifier/Regul) 10 Nov 07 22:58
If the boiler operates at a pressure of > 15 PSIG and 10 HP, then either a 1-hour fire barrier or automatic sprinklers are required. See 2006 International Building Code Table 508.2 for incidental uses.

Your building is protected by an automatic sprinkler system. You should confirm that it complies with NFPA 13. If so, no separation is required.


(Click:

Previous:Chiller unloading curves - TRACE 700 vs6.0   Next:air cooling system for old buildings
[Add TO Favorites] [TOP] [PRINT] [CLOCE WINDOWS]  
  Hot Article
·Convert lux to w/m2
·Moliere diagram
·Carrier HAP 4.2 Data entry pro
·Online/Digital Ductulator
·looking to download a ductulat
·Solar Radiation tables(SHGF) S
·open door heat loss
·blow thru and draw thru AHU?
·Equivalent Full Load Operating
·Preheat coil on AHU - cold cli
·Underground Car Park Ventilati
·Heat Dissipation from a MCC
  Related Articles
·air cooling system for old bui
·Cooling Coil Calculations
·White Rodgers remote sensor f1
·Spiral Pipe Maximum Vacuum
·Induction VAV Vs Normal VAV sy
·Three Way mixing valves
·Acoustical Diffuser Panel Desi
·Common hot and chilled water p
·Condenser Approach
·Exhaust plume calcs
·R-424A and R-434A
·Cooling Load Spreadsheet
Power by DedeCms